Compensation of Systematic Measurement Errors in PMU-based Monitoring Systems for Transmission Grids

Muscas C.;Pegoraro P. A.;Sitzia C.;Solinas A. V.
;
Sulis S.
2021-01-01

Abstract

In the context of modern power systems, the availability of accurate knowledge of line parameters is a requirement to improve any monitoring and control applications. This knowledge is not easy to obtain even in the presence of a monitoring infrastructure of last generation based on Phasor Measurement Units (PMUs). To address this challenge, the paper proposes a method for improving line parameters estimation through the simultaneous estimation of the systematic measurement errors from the instrument transformers. The problem is faced starting from an appropriate modelling of the system, which includes the uncertainties associated with instrument transformers and PMUs. Moreover, the designed algorithm exploits the available constraint equations derived from the network model. The validity of the proposed approach is tested on a portion of the IEEE 14 bus system and confirmed by the presented results.
2021
Inglese
Conference Record - IEEE Instrumentation and Measurement Technology Conference
978-1-7281-9539-1
Institute of Electrical and Electronics Engineers Inc.
2021-
1
6
6
2021 IEEE International Instrumentation and Measurement Technology Conference, I2MTC 2021
Esperti anonimi
2021
virtuale
scientifica
current measurement
instrument transformers
measurement errors
phasor measurement units
power transmission lines
voltage measurement
no
4 Contributo in Atti di Convegno (Proceeding)::4.1 Contributo in Atti di convegno
Muscas, C.; Pegoraro, P. A.; Sitzia, C.; Solinas, A. V.; Sulis, S.
273
5
4.1 Contributo in Atti di convegno
none
info:eu-repo/semantics/conferencePaper
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Questionario e social

Condividi su:
Impostazioni cookie