Optimized Control Structure for a Wastewater Treatment Benchmark

BARATTI, ROBERTO;
2010-01-01

Abstract

In this paper, we define and implement the design of an optimized control structure for the activated sludge process given as COST/IWA benchmark simulation model No.1. Emphasis is given to the identification of controlled variables that contribute to minimize economic costs while the effluent requirements are met. This is achieved considering the self- optimizing procedure as reference method for the controlled variables selection. The proposed optimal control strategy consists of multivariable PID loops which manipulate the airflow rate in the aerobic basins, the nitrate and sludge recirculation flows and the waste sludge flow proportionally to the influent flow such that the overall cost function is minimized. Dynamic simulations validate the resulting optimized controller structure, showing that minimal costs can be achieved.
2010
Inglese
Dynamics and Control of Process Systems
978-3-902661-69-2
Elsevier Science BV
AMSTERDAM
661
666
6
IFAC-DYCOPS Conference
contributo
Esperti anonimi
July 5-7, 2010
Leuven, Belgio
internazionale
Activated sludge process; controlled variables selection; optimal setpoints
4 Contributo in Atti di Convegno (Proceeding)::4.1 Contributo in Atti di convegno
Mulas, M; BRANDAO DE ARAUJO A., C; Baratti, Roberto; Skogestad, S.
273
4
4.1 Contributo in Atti di convegno
none
info:eu-repo/semantics/conferenceObject
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Questionario e social

Condividi su:
Impostazioni cookie