An IEC 61850-Compliant distributed PMU for electrical substations

CASTELLO, PAOLO;MUSCAS, CARLO;
2012-01-01

Abstract

This paper proposes a novel architecture, compliant to IEC 61850, for a distributed IED based phasor measurement unit to be used in electrical substations. In particular, a measurement architecture based on process bus and sampled values synchronized with IEEE 1588-2008 is proposed, so that voltage and current signals are acquired by a Merging Unit, while the signal processing is performed on a IED (Intelligent Electronic Device) that uses a new algorithm for synchrophasor measurement, in compliance with IEEE C37.118.1-2011.
2012
IEEE International Workshop on Applied Measurements for Power Systems, IEEE AMPS 2012
978-1-4673-1539-5
IEEE
42
47
6
2012 IEEE International Workshop on Applied Measurements for Power Systems (AMPS)
contributo
Esperti anonimi
September 26-28, 2012
Aachen, Germany
internazionale
4 Contributo in Atti di Convegno (Proceeding)::4.1 Contributo in Atti di convegno
Castello, Paolo; Ferrari, P; Flammini, A; Muscas, Carlo; Rinaldi, S.